© 2008 Schneider Electric
Communication objects
You can select the following communication objects:
Block X, general:
Parameter
|
Note:
When toggling between operating modes the
"Brightness" and "Times" tabs change.
● Te l e g r a m s
For each movement block the "Action at start of
movement" can be set as a function of the operating
mode.
Normal operation:
– "Send immediately"
– "Do not send"
Master mode:
– "Send immediately"
– "Send immediately and then cyclically"
– "Do not send"
Slave mode:
– "Send immediately and then cyclically" (is
permanent setting in the background of the
application software, is not displayed in the
parameters)
Monitoring mode:
– "Send immediately and then cyclically" (is
permanent setting in the background of the
application software, is not displayed in the
parameters)
The behaviour after the "End of movement time" can
also be set as a function of the operating mode.
Normal operation:
– "Send after staircase timer/remaining time has
elapsed"
– "Do not send"
Master mode:
– "Send after staircase timer/remaining time has
elapsed"
– "Send after staircase timer has elapsed and then
cyclically"
–"Do not send"
Slave mode:
– "Do not send" (is permanent setting in the
background of the application software, is not
displayed in the parameters)
Monitoring mode:
– "Send at end of cycle time when there is movement
and then cyclically" (is permanent setting in the
background of the application software, is not
displayed in the parameters)
Four output objects are available for each of the five
movement blocks and they can be enabled via the
application software. A transmission pause between
the individual output objects can be set for each block.
|
Note:
Five movement blocks and four output objects
per movement detector means that 20
switching/value objects in all are available.
Function Object name Type Prio Flags Behaviour
The
objects
are only
visible in
"Master
mode"
operating
mode.
Block X Master trigger
object
1 bit Low WC Receive
Block X Trigger object 1 bit Low WC Receive
Block X, general
Parameter Setting
Operating mode Normal operation
Master mode
Slave mode
Monitoring mode